HUANG Gang, DENG Demao, PENG Hongjin, WANG Kaibo, WANG Kun, JIN Jiwei. Analysis on an Accident of 110 kV Main Transformer Protection Action Caused by a Developmental Fault on a 110 kV Line[J]. RURAL ELECTRIFICATION, 2023, (7): 16-18. DOI: 10.13882/j.cnki.ncdqh.2023.07.005
Citation: HUANG Gang, DENG Demao, PENG Hongjin, WANG Kaibo, WANG Kun, JIN Jiwei. Analysis on an Accident of 110 kV Main Transformer Protection Action Caused by a Developmental Fault on a 110 kV Line[J]. RURAL ELECTRIFICATION, 2023, (7): 16-18. DOI: 10.13882/j.cnki.ncdqh.2023.07.005

Analysis on an Accident of 110 kV Main Transformer Protection Action Caused by a Developmental Fault on a 110 kV Line

  • The backup grounding impedance protection of the 1# main transformer in a certain 110 kV station tripped the 110 kV buscouple breaker with the first time limit action. At the same time, the zero sequence overcurrent section Ⅱ and distance section Ⅱ protection of a 110 kV line were activated. After successful reclosing, the distance section Ⅱ tripped the line breaker again, causing a voltage loss in the entire station and reducing the power supply reliability of the power grid. This article provides a detailed analysis of the reasons for the protective action of the 110 kV main transformer caused by developmental faults on the 110 kV line and proposes rectification suggestions.