张金博. 某海上风电场35 kV集电线跳闸故障的处理[J]. 农村电气化, 2024, (6): 87-89. DOI: 10.13882/j.cnki.ncdqh.2024.06.022
引用本文: 张金博. 某海上风电场35 kV集电线跳闸故障的处理[J]. 农村电气化, 2024, (6): 87-89. DOI: 10.13882/j.cnki.ncdqh.2024.06.022
ZHANG Jinbo. Handling of 35 kV Collector Line Tripping in a Certain Offshore Wind Farm[J]. RURAL ELECTRIFICATION, 2024, (6): 87-89. DOI: 10.13882/j.cnki.ncdqh.2024.06.022
Citation: ZHANG Jinbo. Handling of 35 kV Collector Line Tripping in a Certain Offshore Wind Farm[J]. RURAL ELECTRIFICATION, 2024, (6): 87-89. DOI: 10.13882/j.cnki.ncdqh.2024.06.022

某海上风电场35 kV集电线跳闸故障的处理

Handling of 35 kV Collector Line Tripping in a Certain Offshore Wind Farm

  • 摘要: 通过对某海上风电场35 kV集电线跳闸进行检查分析,确定集电线断路器跳闸的原因是集电线上连接的3#风机海缆终端头被击穿,造成单相接地故障。3#风机海缆终端头更换后送电时3#风机断路器跳闸,检查发现3#风机断路器TA二次接线端子松动,引起自产零序电流过流,造成零序保护误动,使断路器跳闸。

     

    Abstract: This article analyzes and inspects the tripping of the 35 kV collector line of a certain offshore wind farm, and determines that the cause of the circuit breaker tripping of the collector line is the breakdown of the submarine cable terminal of the 3# wind turbine connected to the collector line, causing a single-phase grounding fault. After replacing the submarine cable terminal of the 3# wind turbine, the circuit breaker of the 3# wind turbine tripped during power transmission. Upon inspection, it was found that the CT secondary wiring terminal of the 3# wind turbine circuit breaker was loose, causing the self-produced zero sequence current to overcurrent, resulting in misoperation of the zero sequence protection and causing the circuit breaker to trip.

     

/