220 kV正母线电压异常事件的原因分析

Cause Analysis of Abnormal Events of 220 kV Positive Bus Voltage

  • 摘要: 基于某220 kV变电站检修改造工作中出现的正母线电压异常事故,从现场施工、专业管理、综合检修统筹管理多方面分析事故的原因。事故发生的直接原因为检修改造中新更换的220 kV母线电压并列装置内部交流电压中性线N接触不良,进而导致220 kV正母线电压互感器二次电压三相不平衡。检修人员重新配线后,线路恢复正常运行。同时,通过专题分析会,对事件原因进行认真分析,对相关责任人进行教育和处理,并提出下一步改进措施,避免同类事件再次发生。

     

    Abstract: Based on the abnormal voltage of the positive bus in a 220 kV substation inspection and repair work, this paper analyzes the causes of the accident from various aspects of on-site construction, professional management, and comprehensive maintenance and overall management. The direct cause of the accident was the poor contact of the internal AC voltage neutral line N of the newly replaced 220 kV bus voltage parallel device during the inspection, modification, and construction, which in turn caused the three-phase imbalance of the secondary voltage of the 220 kV positive bus voltage transformer. After the maintenance personnel rewired, the line resumed normal operation. At the same time, by organizing the person responsible for the incident, professional management and other relevant personnel to hold an accident special analysis meeting, carefully analyze the cause of the incident, educate and deal with the relevant responsible persons, and propose the next improvement measures to avoid the recurrence of similar incidents.

     

/