一起中压单相接地后电压异常的分析

Analysis of an abnormal Voltage after Medium Voltage Single-phase Grounding

  • 摘要: 10 kV中压系统经过接地变和小电阻接地后,引入了电源中性点和零序接地点。对该中压系统发生单相接地后各相电压进行了数学计算和向量分析,得出随着接地电阻增大,故障相电压下降、非故障超前相电压先升高后降低、非故障滞后相电压始终升高的不同变化情况。将计算结果应用于现场一起4TV接线的零序电压互感器极性错误异常,分析结论和实际电压变化现象一致。明确电压异常变化情况发生的机理后,采取正确的纠正行动并及时消除缺陷。

     

    Abstract: After grounding transformer and small resistance grounding, 10 kV medium voltage cabinet introduces power neutral point and zero sequence grounding point. In this paper, the mathematical calculation and vector analysis of each phase voltage after singlephase grounding of the medium voltage cabinet are carried out. With the increase of grounding resistance, the fault phase voltage decreases, the non fault leading phase voltage first increases and then decreases, and the non fault lagging phase voltage always increases. The calculation results are applied to the zero sequence voltage transformer with 4TV connection, and the analysis conclusion is consistent with the actual voltage change. After clarifying the mechanism of abnormal conditions, take correct corrective actions and eliminate defects in time.

     

/