1000 kV电抗器绝缘油含气量异常分析及处理

Analysis and Treatment of Abnormal Gas Content in Insulating Oil of 1000 kV Reactor

  • 摘要: 对变压器(电抗器)绝缘油含气量超标情况进行风险分析,针对一起特高压1000 kV电抗器绝缘油含气量超标,在处理过程中气体始终无法排净的异常情况,由于变压器生产厂家一般外购油枕,且未对油枕进行彻底的检查、试验,设备质量无法保证,针对此现象,提出了含气量超标处理方案,检查处理结束后,采用真空注油、热油循环进行脱气处理。为日后变压器类设备缺陷处理提供参考。

     

    Abstract: This paper analyzes the risk of excessive gas content in transformer (reactor) insulation oil. This paper introduces an abnormal situation that the air content of insulating oil of 1000 kV reactor exceeds the standard and the gas can not be discharged all the time in the treatment process. Since the transformer manufacturer generally purchases the conservator and does not conduct thorough inspection and test on the conservator, the equipment quality cannot be guaranteed. In view of this phenomenon, the treatment scheme of excessive gas content is put forward. After inspection and treatment, vacuum oil injection and hot oil circulation shall be adopted for degassing treatment. It provides a reference for the defect treatment of transformer equipment in the future.

     

/