一起220 kV主变冷控失电保护误动分析

Mal-operation Analysis on Cooling Control Power Failure Protection of 220 kV Transformer

  • 摘要: 雷击导致全站分列的220 kV变电站110 kV Ⅱ母上一条出线故障跳闸,造成该220 kV变电站10 kV Ⅱ母电压波动,10 kV站用电源(由10 kV Ⅱ母供电)自动切换装置动作。在站用电源切换过程中,全站失去交流电源,此时该220 kV变电站的一台强迫油循环风冷变压器冷控失电保护误动作,主变三侧开关跳闸。根据监控机SOE记录和现场保护装置动作记录分析跳闸原因,并指出该事件暴露的问题和提出防范措施。

     

    Abstract: Lightning strike led to the fault tripping of an outlet line on 110 kV Ⅱ bus of the splitting 220 kV substation, resulting in the fluctuation of 10 kV Ⅱ bus voltage of the 220 kV substation, and the automatical switch-device of power supply of the 10 kV station (powered by 10 kV Ⅱ bus) act. In the process of the power switchover, the substation lost the AC power, at this time the cooling control protection of a forced oil circulation air-cooled transformer had a mal-operation in the 220 kV substation, resulting in three breakers of the transformer tripped. According to the monitoring record and the SOE record of field protection device, this paper analyzed the reasons of tripping, pointed out the incident exposed problems, and put forward preventive measures.

     

/